SU42186A1 - Device for protection of three-phase generators with ungrounded neutral from earth faults - Google Patents
Device for protection of three-phase generators with ungrounded neutral from earth faultsInfo
- Publication number
- SU42186A1 SU42186A1 SU140081A SU140081A SU42186A1 SU 42186 A1 SU42186 A1 SU 42186A1 SU 140081 A SU140081 A SU 140081A SU 140081 A SU140081 A SU 140081A SU 42186 A1 SU42186 A1 SU 42186A1
- Authority
- SU
- USSR - Soviet Union
- Prior art keywords
- voltage
- current
- protection
- relays
- earth faults
- Prior art date
Links
- 230000007935 neutral effect Effects 0.000 title claims 2
- 238000004804 winding Methods 0.000 claims description 9
- 230000000903 blocking effect Effects 0.000 description 2
- 238000010586 diagram Methods 0.000 description 2
- 230000016507 interphase Effects 0.000 description 1
- 230000009466 transformation Effects 0.000 description 1
- 238000000844 transformation Methods 0.000 description 1
Landscapes
- Protection Of Generators And Motors (AREA)
Description
Предлагаемое устройство предназначено дл автоматического выключени генератора или дл дачи сигнала при замыкании на корпус (землю) обмоток статора. Отличие предлагаемого устройства от известных заключаетс в том, что синусные ваттметровые реле включены на междуфазовое напр жение и ток нулевой последовательности таким образом, что при замыкани х на землю мощность срабатывани реле определ етс уравнением:The proposed device is designed to automatically turn off the generator or to give a signal when a stator winding closes to the housing (ground). The difference between the proposed device and the known ones is that the sinus wattmeter relays are connected to the interfacial voltage and the zero sequence current so that during ground faults, the relay actuation power is determined by the equation:
-вмф - navy
где ip-TQv. в токовой обмотке реле, бмф - междуфазовое напр жение на зажимах вторичной обмотки трансформатора напр жени .where ip-tqv. in the current winding of the relay, bmf - interfacial voltage at the terminals of the secondary winding of the voltage transformer.
Кроме того, в устройстве применено секционированное заземл ющее сопротивление , дл поочередного выключени секций которого служат реле напр жени .In addition, the device uses a partitioned grounding resistor, for alternately shutting off sections of which serve as voltage relays.
На чертеже изображена принципиальна электрическа схема предлагаемого устройства.The drawing shows a circuit diagram of the proposed device.
Ваттеметровые реле 4, реагирующие на мощностьWattemeter relays 4, responsive to power
W7 /sin9W7 / sin9
приключены токовыми обмотками к (414)adventure current windings to (414)
трансформаторам 1 тока, образующим фильтр токов нулевой последовательности , а обмотками напр жени -к трансформатору напр жени 2 на междуфазовое напр жение.current transformers 1, forming a zero-sequence current filter; and voltage windings, to voltage transformer 2, for an interphase voltage.
Искусственное заземление генератора выполнено помощью секционированного заземл ющего сопротивлени 10, включенного во вторичную цепь заземл ющей реактивной катушки 3.Artificial grounding of the generator is performed using partitioned grounding resistor 10 connected to the secondary circuit of the grounding reactive coil 3.
В устройстве применена блокировка помощью реле максимального напр жени 6, реле минимального напр жени 8 и реле времени 7, которой достигаетс увеличение величины тока замыкани на землю при замыкании на землю на определенной части витков генера тора.The device uses a blocking using the overvoltage relay 6, the undervoltage relay 8 and the time relay 7, which achieves an increase in the earth fault current when short to earth on a certain part of the generator turns.
При замыкани х на землю в защищаемой зоне (между трансформаторами тока 1 и нулем генератора, если обмотки генератора соединены в звезду) во вторичной цепи трансформаторов тока 1 протекает ток замыкани на землю поврежденной фазы (трансформированное значение), определ емый величиной заземл ющего сопротивлени и коэфициентом трансформации трансформаторов тока.When ground faults are in the protected zone (between current transformers 1 and the generator zero, if the generator windings are connected in a star), a fault current ground fault current (transformed value) determined by the value of grounding resistance and coefficient flows in the secondary circuit of current transformers 1 transformations of current transformers.
Напр жение между неповрежденными фазами остаетс практически посто нным и образует с током поврежденнойThe voltage between the intact phases remains almost constant and forms with the current damaged
фазы угол в 90°. Напр жение между поврежденной и не поврежденной фазой может мен тьс по величине и направлению в некоторых пределах. При замыкани х на землю на любой из фаз генератора одно из трех ваттметровых реле будет реагировать на мощностьphase angle of 90 °. The voltage between the damaged and non-damaged phase may vary in magnitude and direction within certain limits. When grounding on any of the generator phases, one of the three watt-meter relays will react to power
.вмф .VMF
а два других реле будут реагировать на мощностьand the other two relays will respond to power
IF-0,5 ip IF-0.5 ip
Действие блокировки заключаетс в следующем. В нормальных услови х заземл ющее сопротивление 10 включено полностью; при замыкани х на землю приходит в действие реле повышени напр жени 6 и включает реле времени 7. В зависимости от величины напр жени на зажимах заземл ющей катушки S или тока, протекающего через заземл ющую катушку, а следовательно в зависимости от того, нл какой части обмотки статора происходит замыкание на землю, приход т в действие реле минимального напр жени 8, включа секции заземл ющего сопротивлени таким образом, чтобы обеспечивалась требуема из расчета величина тока замыкани на землю. Следует отметить, что контакты реле 7 и 5 должны быть рассчитаны на разрыв и включение цепи тока во вторичной обмотке реактивной катушки 3 и поэтому при практическом выполнении устройства могут быть заменены автоматами , приводимыми в действие от соответствующих реле.The blocking action is as follows. Under normal conditions, grounding resistance 10 is fully on; during ground faults, voltage boost relay 6 is activated and switches on time relay 7. Depending on the voltage value at the terminals of the grounding coil S or the current flowing through the grounding coil, and therefore depending on what part the stator winding is short-circuited to earth, the minimum voltage relay 8 is activated, including the grounding resistance sections in such a way as to ensure the required ground fault current. It should be noted that the contacts of the relay 7 and 5 must be designed to break and turn on the current circuit in the secondary winding of the reactive coil 3 and therefore, in the practical implementation of the device, they can be replaced by automatics driven by the corresponding relays.
Устройство не ограничивает число ступеней заземл ющего сопротивлени (на чертеже показана схема с четырьм ступен ми заземл ющего сопротивлени ).The device does not limit the number of grounding resistance levels (the drawing shows a diagram with four grounding resistance levels).
Врем действи реле времени 7 должно быть больше времени действи реле минимального напр жени 8.Time of operation of time relay 7 must be greater than the time of operation of minimum voltage relay 8.
Показанное на чертеже реле времени 9 назначено дл размыкани вторичной цепи заземл ющей реактивно катушки 5 при длительном замыкании на землю и тем самым дл прекращени протекани тока заземлени через место повреждени .The time relay 9 shown in the drawing is assigned to open the secondary circuit of the earthing jet coil 5 during a long circuit to earth and thereby to stop the flow of the ground current through the fault site.
По расчету автора подобной схемой включений ваттметровых реле достига тс существенное уменьшение процента незащищенных витков.According to the author's calculation, using a similar scheme for switching on wattmeter relays, a significant reduction in the percentage of unprotected turns is achieved.
Предмет изобретени .The subject matter of the invention.
Claims (2)
Priority Applications (1)
| Application Number | Priority Date | Filing Date | Title |
|---|---|---|---|
| SU140081A SU42186A1 (en) | 1934-01-05 | 1934-01-05 | Device for protection of three-phase generators with ungrounded neutral from earth faults |
Applications Claiming Priority (1)
| Application Number | Priority Date | Filing Date | Title |
|---|---|---|---|
| SU140081A SU42186A1 (en) | 1934-01-05 | 1934-01-05 | Device for protection of three-phase generators with ungrounded neutral from earth faults |
Publications (1)
| Publication Number | Publication Date |
|---|---|
| SU42186A1 true SU42186A1 (en) | 1935-03-31 |
Family
ID=48356918
Family Applications (1)
| Application Number | Title | Priority Date | Filing Date |
|---|---|---|---|
| SU140081A SU42186A1 (en) | 1934-01-05 | 1934-01-05 | Device for protection of three-phase generators with ungrounded neutral from earth faults |
Country Status (1)
| Country | Link |
|---|---|
| SU (1) | SU42186A1 (en) |
-
1934
- 1934-01-05 SU SU140081A patent/SU42186A1/en active
Similar Documents
| Publication | Publication Date | Title |
|---|---|---|
| SU42186A1 (en) | Device for protection of three-phase generators with ungrounded neutral from earth faults | |
| RU2160953C2 (en) | Method for single-phase fault detection in low- voltage line including ground-fault current correction (alternatives) | |
| US4525764A (en) | System for disconnecting an electrical power source from a load | |
| GB566584A (en) | Improvements in and relating to protective arrangements for star-connected electrostatic condensers | |
| Khan et al. | Analysis of faults and protection schemes for magnetically controlled shunt reactor | |
| Hunter | Some engineering features of Petersen coils and their application | |
| McNabb et al. | Transient Design Studies for the Transmantaro Series-Compensated Transmission System | |
| US2336872A (en) | Protection of alternating current electric power systems | |
| SU51480A1 (en) | Device for increasing the power supplied to the relay by the direction of energy in earth fault protection with incomplete grounding | |
| SU64905A1 (en) | Device for preventing malfunctioning of fast acting distance protection with between phase faults in the voltage circuit | |
| SU43952A1 (en) | Device to protect multi-phase electrical installations with insulated neutral against earth faults | |
| SU62600A1 (en) | Device to protect the rotor winding of a synchronous generator from ground fault | |
| SU73839A1 (en) | Isolation control device in high voltage three-phase networks | |
| RU178102U1 (en) | PROTECTIVE SHUT-OFF DEVICE | |
| Khamitovich et al. | MICROPROCESSOR PROTECTION OF SYNCHRONOUS GENERATORS AT POWER PLANTS | |
| SU936202A1 (en) | Device for grounding power transformer neutral wire | |
| RU2284082C2 (en) | Protective device for electrical equipment of high-voltage substations and power transmission lines | |
| US2000693A (en) | System impervious to unbalanced faults | |
| RU2007007C1 (en) | Device for protection of transformer connected to power line via isolating switch | |
| SU63590A1 (en) | Device for distance protection of three-phase high-voltage installations | |
| SU48728A1 (en) | Device for differential protection of electric generators | |
| Chester | Electrical protection | |
| RU1836774C (en) | Internal surge and ferroresonance process limiting arrangement for systems with compensated capacitive fault-to earth current | |
| Basu et al. | Application of single-pole auto reclosing of circuit breakers in ehv transmission line with capacitance grounding | |
| SU1761A1 (en) | Device for protection of three-phase installations from single-phase earth faults |