Background
In a voltage network of 35kV or below, three-stage current protection consisting of non-time-limit current quick-break protection (current I stage protection), time-limit current quick-break protection (current II stage protection) and timed overcurrent protection (current III stage protection) is widely used as a protection scheme for interphase short circuit of a power transmission line.
The three-stage current protection is simple and reliable, and can meet the requirement of quickly removing faults under normal conditions, but the three-stage current protection also has the defect of being directly influenced by the connection mode of a power grid and the operation mode change of a power system, for example, a current setting value must be selected according to the maximum operation mode of the system, and the sensitivity must be verified by the minimum operation mode of the system, so that the three-stage current protection cannot meet the requirement of the sensitivity or the protection range.
In the network shown in fig. 1, the phase voltage of the power supply is E
GMaximum equivalent impedance of Z
s maxMinimum equivalent impedance of Z
s minLine impedance per unit length of Z
1Then, according to the conventional three-stage current protection calculation methodCurrent I section protection constant in the network
The calculation formula is shown as formula (1), wherein
The reliability coefficient of the current I section protection is usually 1.2-1.3.
Under the setting value, the calculation formula of the minimum protection range of the current I section protection is shown as the formula (2).
The protection range of the current I section protection is mainly influenced by factors such as the system operation mode, the fault type and the like. If the system mode of operation changes significantly (i.e. Z)s maxAnd Zs minWith a large difference in value), the protection range of the current I segment protection is small or even completely out.
Disclosure of Invention
In order to solve the problems, the invention provides a three-section type current protection current setting device and method with a large protection range, which can set the fixed value of current I section protection under different short-circuit fault types and different operation modes, greatly increase the protection range of the current I section protection under the dynamic fixed value, and improve the protection sensitivity.
In order to achieve the purpose, the technical scheme adopted by the invention is as follows: a three-stage current protection current setting device with large protection range is arranged in a system power supply ESAnd a high-frequency power supply E is additionally arranged on the power transmission line between the AB of the power transmission line consisting of the circuit breakerss1High pass filter, knife switch QS1、QS2And two groups of high-frequency wave-traps respectively arranged at A, B-phase sides and outsideApplying high frequency power supply Es1Through a knife switch QS1Connected between two high-frequency wave traps and near to phase A, and high-pass filter passing through knife switch QS2And the two high-frequency wave trappers are connected between the two groups of high-frequency wave trappers and close to one side of the phase B.
The system power supply ESHas a power supply phase voltage of EGFrequency f0Is 50HZ(ii) a The external high-frequency power supply Es1Has a power supply phase voltage of E1Frequency of f1And satisfy E1<<EGAnd f1>>f0. The high-pass filter is at frequency f1Time-parallel resonance at frequency f0High impedance is presented. The high-frequency wave trap is at frequency f0Presents a low impedance at high frequencies f1High impedance is presented. The knife switch QS1、QS2The opening and closing of the device are controlled by a microcomputer protection device.
The method for setting the current by using the device comprises the following steps:
in normal operation, the knife switch QS
1、QS
2All are in open state, when the system operation mode changes, the microcomputer protection device controls the knife switch QS
2First closed, high frequency power supply E
s1Putting the mixture into a system for operation; thereupon, the microcomputer protection device controls the knife switch QS
1Closed due to the high-pass filter at frequency f
1Is parallel resonant, corresponding to the manufacture of the high-frequency power supply E
S1Is short-circuited at frequency f
1High frequency short circuit current of
Collecting the current by a microcomputer protection device;
at the same time, high frequency short circuit current
The calculation can be performed using equation (5);
therefore, R and L can be calculated as shown in equations (6) and (7), respectively:
the microcomputer protection device can calculate that the resistance part of the system impedance is R and the reactance part is R under the operation mode at the time according to the values of R and L
Dynamic impedance value Z of the system at power frequency
s is movedThe calculation can be performed by equation (8);
then through the dynamic impedance value Z
s is movedCalculating the protection constant value of the current I section in the network
The calculation formula is shown as formula (4)
In the formula (4)
The reliability coefficient for current I section protection is usually 1.2-1.3
The fixed value of the current I section protection under different short-circuit fault types and in different operation modes can be set through the formula (4);
when the microcomputer protection device calculates the dynamic impedance value Zs is movedLater, the device sends out a tripping command to control the switch QS1And knife switch QS2Open and ready to close again the next time the system mode of operation changes.
Compared with the prior art, the invention has the beneficial effects that:
the three-section type current protection current setting device and the method with the large protection range calculate the protection constant value of the current I section in the network through the dynamic impedance value. The fixed value of the current I section protection under different short-circuit fault types and different operation modes can be set through the dynamic impedance value, the protection range of the current I section protection is greatly enlarged under the dynamic fixed value, and the protection sensitivity is improved.
In the knife switch QS
1When closed, the high-pass filter is at power frequency f
0It presents a high impedance when it is applied to the system power supply E
SThe device is equivalent to normal operation and has no influence at all; when the microcomputer protection device controls the knife switch QS
2And QS
1Closed, high frequency power supply E
s1Corresponding to the occurrence of a three-phase short-circuit fault with a short-circuit current of
But due to E
1<<E
GShort circuit current
The size is very small, and the damage to the power transmission line and the electrical equipment can not be caused.
Detailed Description
In view of the disadvantage of the prior art that the protection range of the protection of the current I section is very small or even completely not, the invention improves the following two aspects when the fixed value of the protection of the current I section is set.
First, for the line end short circuit current in equation (1), a fixed short circuit current I is not usedk maxInstead, three forms of three-phase short circuit, two-phase short circuit grounding and two-phase short circuit are distinguished, different short circuit current values are calculated by using different calculation formulas respectively, and three different protection fixed values are set, specifically as shown in formula (3).
When a short-circuit fault occurs in a line, various criteria can quickly judge which fault is. For example, A, B, C three-phase current is suddenly increased by many times, and it is judged that a three-phase short-circuit fault occurs in a line; according to the method, two-phase current in A, B, C three-phase current is increased by many times, the other phase current is basically unchanged, and obvious zero-sequence current exists in a system, so that the two-phase short-circuit ground fault in a circuit is judged; the method is characterized in that two-phase current in A, B, C three-phase current is increased by multiple times, the other phase current is basically unchanged, and zero-sequence current does not exist in a system, so that two-phase short-circuit fault in a circuit is judged.
When the microcomputer protection device judges which kind of short-circuit fault occurs in the line, the corresponding setting current value is called immediately, and the setting value is used as the protection setting value of the current I section protection under the short-circuit fault. After the method is used, the problem that the set current values are different due to different fault types to influence the protection area of the current I section can be solved.
Secondly, when the formula (1) is used for calculating the I-section protection setting value of the current, the used equivalent impedance of the power supply adopts the minimum impedance Zs minThe static impedance is adopted, in fact, when the circuit runs, the equivalent impedance of the power supply is a dynamically changed impedance value along with the change of the running mode, and if the sum Z of the equivalent impedance of the power supply and the impedance of the circuit when the short-circuit fault occurs can be dynamically measureds is movedThen equation (3) can be written as equation (4).
In order to dynamically measure the sum Z of the equivalent impedance of the power supply and the line impedance when short-circuit fault occurss is movedThe invention designs a three-section current protection current setting device, which is arranged in a system power supply E as shown in figure 2SAnd a high-frequency power supply E is additionally arranged on the power transmission line between the AB of the power transmission line consisting of the circuit breakerss1High pass filter, knife switch QS1、QS2And two high-frequency wave traps respectively arranged at A, B phase sides and externally provided with a high-frequency power supply Es1Through a knife switch QS1Connected between two high-frequency wave traps and near to phase A, and high-pass filter passing through knife switch QS2And the two high-frequency wave trappers are connected between the two groups of high-frequency wave trappers and close to one side of the phase B.
Wherein, the system power supply ES(element ① in the figure), the mains phase voltage is EGFrequency f0Is 50HZ. With the addition of a high-frequency power supply Es1(element ② in the figure), the mains phase voltage is E1Frequency of f1And satisfy E1<<EGAnd f1>>f0A high pass filter (element ③ in the figure) designed to be at frequency f1Time-parallel resonance at frequency f0Presenting a high impedance, high frequency wave trap (element ④ in the figure), designed to operate at a frequency f0Low impedance, convenient transmission of power frequency electric energy, high frequency f1High impedance is presented to make high frequency power supply Es1The generated high-frequency power is not transmitted to the circuit except the AB circuit, so that the high-frequency power is prevented from being lost and affecting the operation of other circuits.
In addition to wiring the conventional three-stage current microcomputer protection device, the microcomputer protection device needs to have the following wiring added, as shown in fig. 3. Controlling knife switch QS through microcomputer protection device
1(element ⑤ in the figure), QS
2(
element ⑥ in the figure.) switch QS is operated at ordinary times
1、QS
2All are in open state, when the system operation mode changes, the microcomputer protection device controls the knife switch QS
2First closed, high frequencyPower supply E
s1Putting into the system for operation. Thereupon, the microcomputer protection device controls the knife switch QS
1Closed due to the high-pass filter at frequency f
1Is parallel resonant, corresponding to the manufacture of the high-frequency power supply E
S1Is short-circuited at frequency f
1High frequency short circuit current of
The current is collected by a microcomputer protection device.
At the same time, high frequency short circuit current
The calculation can be performed using equation (5).
Therefore, R and L can be calculated as shown in equations (6) and (7), respectively:
the microcomputer protection device can calculate that the resistance part of the system impedance is R and the reactance part is R under the operation mode at the time according to the values of R and L
Dynamic impedance value Z of the system at power frequency
s is movedThe calculation can be performed by equation (8).
Finally, in combination with formula (4), the dynamic impedance value Z can be used
s is movedCalculating the protection constant value of the current I section in the network
Namely, the fixed value of the current I section protection under different short-circuit fault types and different operation modes can be set through the formula (4), and under the dynamic fixed value, the protection range of the current I section protection is greatly enlarged, and the protection sensitivity is improved.
When the microcomputer protection device calculates the dynamic impedance value Zs is movedLater, the device sends out a tripping command to control the switch QS1And knife switch QS2Open and ready to close again the next time the system mode of operation changes.
The foregoing is merely exemplary and illustrative of the principles of the present invention and various modifications, additions and substitutions of the specific embodiments described herein may be made by those skilled in the art without departing from the principles of the present invention or exceeding the scope of the claims set forth herein.