Invalid destination TSAP during physical reconnect
IEC61850 IED Explorer in .net
Status: Beta
Brought to you by:
pavel-ch
IEDExplorer sends a wrong destination TSAP in the CR connect request when reconnecting under following pre-condition:
1) Connect IEDExplorer to the server IED
2) Then unplug ethernet cable to disconnect (servers side)
3) Replug ethernet cable --> IEDExplorer tries to reconnect (fails)
Reason: Some IEDs won't reconnect if wrong TSAP is received.
Hello Wojtek, I think this was solved by the commit [32cc18] from 2.9.2017, unfortunatelly the .exe has not been released since that time. Can you try to build from source? Br Pavel
Related
Commit: [32cc18]
Hi Pavel,
Ok, I rebuilt the latest sources to confirm the issue has gone.
Looks fine, thanks a lot. Br Wojtek